Place of Origin: | England |
Brand Name: | MTL |
Model Number: | MTL5581 |
Minimum Order Quantity: | 1pc |
---|---|
Packaging Details: | carton |
Delivery Time: | in stock |
Payment Terms: | T/T payment |
Supply Ability: | 100pcs |
MTL5581 (Isolator for low-level signals)
MTL5581 takes a low-level dc signal from a voltage source in a hazardous area, isolates it, and passes it to a receiving instrument located in the safe area. The module is intended for use with thermocouples utilising external cold-junction compensation. A switch enables or disables the safety drive in the event of thermocouple burnout or cable breakage; a second switch permits the selection of upscale or downscale operation as appropriate.
MTL5581 SPECIFICATION
See also common specification
Number of channels
One
Signal source
Any dc millivolt source
Location of millivolt source
Zone 0, IIC, T4–T6 hazardous area if suitably certified
Div. 1, Group A, hazardous location
Input and output signal range
0 to ± 50mV, overrange to ± 55mV
Maximum lead resistance 600Ω
Output resistance
60Ω nominal
Transfer accuracy@20°c
Linearity and repeatability < 0.05% of reading or ± 5μV,
Whichever is the greater
Temperature drift
< 2μV/°C, maximum
Response time
Settles to within 10% of final value within 150μs
Frequency response
dc to 4kHz nominal
Safety drive on THc burnout
Two switches enable or disable the safety drive and select
Contact Person: Ms. Steven